In short
A rebar pull-out test pulls a post-installed bar along its axis to a load the designer sets, to check it was installed and bonded properly. Staht's rebar adaptors, R6 to R25, are made for its hydraulic heavy duty kits, to 176 or 358 kN, not for the 25 and 60 kN pull testers. The designer also sets how many bars to test and what counts as a pass.
This guide explains how site tests are planned and carried out under BS 8539:2012+A1:2021. It does not replace the standard, the anchor manufacturer's data, or the instructions of the specifier or engineer responsible for the job, who decides the test plan, the loads and the factors. A test records what happened on the day; it does not approve a fixing for use.
Key figures
| Staht heavy duty kits | 176 kN (18 t cylinder) or 358 kN (36 t cylinder), each with a 51 mm stroke |
|---|---|
| Rated pressure of the pump and cylinders | 700 bar |
| Rebar adaptors | R6, R8, R10, R12, R14, R16, R20, R22 and R25, from £43 ex VAT |
| Load from pressure | Load in kN = pressure in bar × piston area in cm² ÷ 100: 25.1 cm² on the 18 t, 51.2 cm² on the 36 t |
| Gauge | Staht G1 Pro, to 1000 bar, accurate to 0.25% of full scale |
| Kits, ex VAT | 18 t £3,850; 36 t £4,750; both cylinders £5,995 |
| Who sets the test load | The designer or the engineer responsible for the connection |
What is a rebar pull-out test?
A rebar pull-out test pulls a reinforcing bar along its own axis with a hydraulic cylinder, and records the load it held and what happened. On site it's done on post-installed bars: straight deformed bars set in mortar in holes drilled in hardened concrete, to join new concrete to old, such as starter bars for a new slab, wall or column. EOTA's assessment document for these systems is EAD 330087-01-0601; it also covers post-installed bars used as tension anchors. Each system's European Technical Assessment says how it's installed and what it can carry.
A post-installed bar holds by the bond of its mortar, so it depends on how the hole was drilled, cleaned and filled, and on the mortar curing. That's what a site test checks. A cast-in bar is placed before the concrete is poured, and its anchorage is part of the reinforced concrete design to EN 1992-1-1: there's no drilled hole or mortar to check.
When is rebar pull-out tested?
When the designer specifies it: usually as proof tests on a sample of the post-installed bars once the mortar has cured, and to failure only if the designer asks.
- Proof tests load a sample of the bars installed for the job to a set load, to check they were installed correctly. The bars stay in use. A proof test checks the installation, not whether the design is right.
- Tests to failure are done only if the designer asks for them, on bars installed just for the test, to find what the bars hold in that concrete.
- Timing: test a bonded bar only after at least the mortar maker's recommended curing time.
The designer or engineer responsible for the connection sets the test load, how many bars to test and what counts as a pass. BS 8539, the code of practice for post-installed anchors, notes that a site test checks tension only (where a bar also carries shear, the engineer decides whether to raise the load) and shows performance only in uncracked concrete. For the rules on site, see rebar and holding-down bolt testing.
Which Staht tester do I need for rebar?
A heavy duty kit. The t25 and t60 pull testers test anchors and eyebolts up to 25 kN and 60 kN, and Staht's rebar adaptors don't fit them. Each heavy duty kit has a two-stage aluminium hand pump rated to 700 bar, a hollow bore cylinder on a steel baseplate, a 3 m high-pressure hose with quick connectors and the G1 Pro digital Bluetooth gauge, in a wheeled Peli case. Choose the kit by the highest load you'll apply, and check with us that the cylinder suits your bar size: the 18 t cylinder's bore is 26 mm, the 36 t's 39 mm. For loads below about 13 kN, the 18 t cylinder reads more closely (see below).
Staht testers for rebar, by load
| Tester | Capacity | Cylinder | Kit weight | Price |
|---|---|---|---|---|
| Heavy duty kit, 18 t (800-000) | 176 kN | 51 mm stroke; 25.1 cm² piston area; 171 mm tall | 17.9 kg | £3,850 ex VAT |
| Heavy duty kit, 36 t (800-001) | 358 kN | 51 mm stroke; 51.2 cm² piston area; 261 mm tall | 26.7 kg | £4,750 ex VAT |
| Heavy duty kit, 18 t and 36 t (800-004) | 176 kN or 358 kN | Both cylinders, as above | 29.7 kg | £5,995 ex VAT |
| t25 or t60 pull tester | 25 kN or 60 kN | Not for rebar: no rebar adaptor fits them | – | – |
What's in a heavy duty kit
The 18 t kit, the 36 t kit or the kit with both cylinders, each with its pump, cylinder, hose and G1 Pro gauge packed in a wheeled Peli case with a foam insert. Rebar adaptors are bought separately, one for each bar size you test.

Which rebar adaptor fits which bar?
| Adaptor | Part number | Weight | Price | Bar's yield force, B500 (not the adaptor's rating) |
|---|---|---|---|---|
| R6 (6 mm bar) | 800-006 | 0.35 kg | £43 ex VAT | 14.1 kN |
| R8 (8 mm bar) | 800-007 | 0.34 kg | £45 ex VAT | 25.1 kN |
| R10 (10 mm bar) | 800-008 | 0.58 kg | £46 ex VAT | 39.3 kN |
| R12 (12 mm bar) | 800-009 | 0.59 kg | £46 ex VAT | 56.5 kN |
| R14 (14 mm bar) | 800-010 | 0.58 kg | £53 ex VAT | 77.0 kN |
| R16 (16 mm bar) | 800-011 | 0.54 kg | £55 ex VAT | 100.5 kN |
| R20 (20 mm bar) | 800-012 | 1.41 kg | £115 ex VAT | 157.1 kN |
| R22 (22 mm bar) | 800-013 | 2.10 kg | £200 ex VAT | 190.1 kN |
| R25 (25 mm bar) | 800-014 | 2.04 kg | £262 ex VAT | 245.4 kN |
Why the table gives the bar's yield force
The last column is the load at which a grade B500 bar starts to yield, the grade BS 4449 sets for UK reinforcing bar: 500 N/mm² times the bar's nominal area (π × d² ÷ 4). A 16 mm bar's area is 201.1 mm², so its characteristic yield force is 100.5 kN. A proof load is kept below it, so the bar isn't stretched. It's a reference, not a test load: the designer sets the load. It isn't the adaptor's rating either: Staht doesn't publish a rated load for the rebar adaptors, so ask us before testing a bar near its yield force.
What pressure for my test load?
How do you set up a rebar pull-out test?
- Get the load and check the bar
Get the test load, the number of bars to test and the pass criterion from the designer or engineer responsible. Check the mortar has had at least its maker's recommended curing time.
- Choose the kit and the adaptor
Use the kit whose capacity covers the test load, 176 kN or 358 kN, and whose 51 mm stroke is longer than the movement you expect. Check with us that its cylinder suits the bar size. Take the rebar adaptor marked with the bar's size.
- Set up the cylinder and adaptor
Fit the rebar adaptor marked with the bar's size and connect it to the cylinder as Staht shows you. Stand the cylinder on its steel baseplate on sound, flat concrete, square to the bar so it pulls along the bar's axis. If you're not sure how the adaptor connects, or how far the bar must stand out, ask us before you test. On walls and soffits, secure the rig so it can't fall.
- Connect the hydraulics and the gauge
Join the pump to the cylinder with the 3 m hose's quick connectors, and fit the G1 Pro gauge with its G1/4 seal in place and the fitting tight.
- Set up the app
Switch on the G1 Pro and connect it to the free Staht Connect app. Choose the cylinder (25.1 cm² for the 18 t, 51.2 cm² for the 36 t) and confirm its area and the number of cylinders: the test can't start until you do. Set the target load.
- Load it steadily
Pump steadily, watching the load in kN in the app and the pressure in bar on the gauge, up to the test load. Never go past 700 bar. Hold for as long as the specification says, while the app counts the hold down. Keep everyone out of line with the bar while it's loaded.
- Release and record
Release the pressure at the pump. Save the result with its pass or fail, the peak load, photos and location, then note anything you saw before moving to the next bar.
How do you read the result?
Load is pressure times the piston area: load in kN = pressure in bar × piston area in cm² ÷ 100. The app shows the load from the cylinder you confirmed, and the G1 Pro's own screen shows the pressure, live and peak. The G1 Pro is accurate to 0.25% of its 1000 bar full scale, ±2.5 bar: ±0.63 kN on the 18 t cylinder and ±1.28 kN on the 36 t. On the 36 t, that's more than the 10% of reading BS 8539 asks of a gauge below about 12.8 kN, so use the 18 t for small loads.
- A pass meets the criterion in the specification. For post-installed anchors, BS 8539's is that the anchor holds the proof load with no movement, damage or deformation.
- A failure: stop, record what happened, and tell whoever asked for the test. The designer decides what happens next.
- In a test to failure, record the load at first movement, the peak load and how it failed: the bar pulling out with its mortar, the mortar parting from the bar, the steel yielding or breaking, or a cone of concrete coming away. A baseplate bearing close to the bar holds the concrete down, so a cone can't fully form: BS 8539 recommends supports well clear of the anchor for tests to failure, and noting it when they aren't. Ask the designer how the rig should bear. See first movement and failure modes.
Pressure for each test load
| Test load | 18 t cylinder (25.1 cm²) | 36 t cylinder (51.2 cm²) |
|---|---|---|
| 25 kN | 99.6 bar | 48.8 bar |
| 50 kN | 199.2 bar | 97.7 bar |
| 75 kN | 298.8 bar | 146.5 bar |
| 100 kN | 398.4 bar | 195.3 bar |
| 125 kN | 498.0 bar | 244.1 bar |
| 150 kN | 597.6 bar | 293.0 bar |
| 175 kN | 697.2 bar | 341.8 bar |
| 200 kN | Over 700 bar: use the 36 t | 390.6 bar |
| 250 kN | Over 700 bar: use the 36 t | 488.3 bar |
| 300 kN | Over 700 bar: use the 36 t | 585.9 bar |
| 350 kN | Over 700 bar: use the 36 t | 683.6 bar |
Worked out as pressure in bar = load in kN × 100 ÷ piston area in cm², to one decimal place. The 18 t cylinder reaches 175.7 kN at 700 bar and the 36 t 358.4 kN. For any other cylinder, use the hydraulic pressure to force calculator.
What should the record show?
Everything an anchor test report records, plus:
- the bar size and the adaptor used;
- the cylinder and its piston area;
- the pressure read as well as the load;
- the mortar and when the bars were installed, so the curing time can be checked.
Use our free anchor test report template, a fillable PDF, or the Staht Connect app, which saves each test with its peak, pass or fail, photos and location, for reports from the web dashboard.
Staying safe at high loads
- The cylinder's 51 mm stroke must be longer than the movement you expect.
- Every part that carries load must be strong enough, with a margin. Check them before each test.
- Never go past 700 bar on the pump and cylinders, or 1000 bar on the gauge.
- Secure the rig on walls and soffits.
- Wear safety boots, work gloves and eye protection as a minimum, as the G1 Pro's manual says.
- The kit is for a competent person: someone trained and experienced in the test and the app.
- Our advice: keep everyone out of line with the bar while it's loaded.
Have the G1 Pro calibrated every year: Staht offers pressure gauge calibration up to 1000 bar.
More questions
A hydraulic heavy duty kit, a rebar adaptor for each bar size, and a way to record the result. Staht's kits have a hand pump, a hollow bore cylinder (176 kN or 358 kN), a hose and the G1 Pro Bluetooth gauge, and the free Staht Connect app records each test. See heavy duty testers.
No. Staht's rebar adaptors are for the heavy duty kits. The t25 and t60 reach 25 kN and 60 kN on threaded anchors and eyebolts.
The one marked with the bar's size: R6, R8, R10, R12, R14, R16, R20, R22 or R25, for bars of 6 to 25 mm. They're £43 to £262 ex VAT and bought separately from the kit.
The load the designer or the engineer responsible for the connection sets. As a check, it should be well below the bar's yield force (100.5 kN for a 16 mm B500 bar); if it isn't, ask the designer, and ask us about the adaptor, before you test.
About 398 bar on the 18 t cylinder (25.1 cm²) and 195 bar on the 36 t (51.2 cm²). The Staht Connect app shows the load in kN as you pump.
The 36 t kit: it reaches 358 kN, where the 18 t kit stops at 175.7 kN (700 bar).
Only if the designer asks for it. A proof test stops at the test load and the bar stays in use; tests to failure are done on bars installed for the test.
Only after at least the mortar maker's recommended curing time.
Site pull-out tests are for post-installed bars: their hold depends on how they were installed. A cast-in bar's anchorage is part of the reinforced concrete design, with no drilled hole or mortar to check.
The bar size it grips: R10 is for 10 mm bar, R16 for 16 mm bar.
Related pages
- Rebar adaptors and heavy duty rebar test kits: sizes, part numbers and prices
- Rebar and holding-down bolt testing: who sets the load, what a test shows, safety
- Connecting a pull tester to the anchor: adaptors for every kind of fixing
- Hydraulic pressure to force: bar to kN for any cylinder
- Anchor test load calculator: BS 8539 preliminary test loads for post-installed anchors
- Anchor test report template: a free fillable PDF
Sources
- EAD 330087-01-0601 Systems for post-installed rebar connections with mortar, EOTA
- BS 8539:2012+A1:2021 Code of practice for the selection and installation of post-installed anchors in concrete and masonry, BSI
- BS 4449:2005+A3:2016 Steel for the reinforcement of concrete: weldable reinforcing steel, bar, coil and decoiled product, BSI
- BS EN 1992-1-1 Eurocode 2: Design of concrete structures, general rules and rules for buildings, BSI
- Staht Heavy Duty Test Kits, Technical Datasheets No 170, 171 and 172, Staht
- Staht 18 t and 36 t cylinders, Technical Datasheets No 186 and 187, Staht
- Staht Rebar Adaptors R6 to R25, Technical Datasheets No 173 to 181, Staht
- Staht Heavy Duty Test Kit brochure, Staht
- Staht G1 Pro gauge user manual, Revision 1, 04/02/2026, Staht