Industry: construction

Anchor testing on construction sites

Ukratko

Post-installed anchors in concrete and masonry are selected, installed and tested under BS 8539:2012+A1:2021. Site tests do two jobs: finding what an anchor can carry where there's no data for the base material, and proof testing a sample of installed anchors to check they went in properly. The specifier sets the tests and loads; the tester records facts; the specifier decides what they mean.

Ove smjernice objašnjavaju kako se ispitivanja na gradilištu planiraju i provode prema normi BS 8539:2012+A1:2021. One ne zamjenjuju normu, podatke proizvođača sidara niti upute projektanta ili inženjera odgovornog za radove, koji određuje plan ispitivanja, opterećenja i faktore. Ispitivanje bilježi ono što se dogodilo na dan ispitivanja; ono ne odobrava pričvršćenje za uporabu.

Key figures

Proof sampleAt least 2.5% of anchors and at least 3, with at least 3 in each discrete area
Proof loadN_Ek × 1.5 at 2.5% tested, or × 1.25 at 5%; no more than 1.5 × the maker's recommended load
PassHolds the proof load without movement, or damage to the anchor or base material
Allowable-load testsMostly in masonry, on anchors installed for the test and not used after
Bonded anchorsTested only after at least the maker's recommended curing time

Who is this page for?

Fixings installers, main contractors, M&E and façade contractors, and temporary works coordinators: anyone who specifies, installs, tests or relies on anchors drilled into concrete, brick or block. Scaffold tie anchors have their own guidance: see scaffolding.

Which rules and standards apply?

DocumentFromWhat it means for anchors
BS 8539:2012+A1:2021BSIThe code of practice for selecting and installing post-installed anchors in concrete and masonry, including site tests. Current, under review
European Technical Assessments (ETAs)Assessment bodies, to EOTA's EADsAn anchor's assessed performance and conditions of use. For bonded anchors in concrete the current assessment document is EAD 330499-02-0601
CDM Regulations 2015, regulation 19UK legislationAny temporary support or structure must be "of such design and installed and maintained so as to withstand any foreseeable loads which may be imposed on it"
BS 5975-1:2024BSIProcedures for controlling temporary works. It and BS 5975-2:2024 replaced BS 5975:2019, withdrawn in December 2024
Work at Height Regulations 2005UK legislationFor anchors used with fall protection on site: see [height safety](/industries/height-safety)

When do anchors need site tests?

To find what an anchor can carry: only where the maker has no data for the base material. That is rare in concrete, because BS 8539 recommends anchors with an ETA, and is mostly needed in masonry or where the concrete's condition is in doubt. No tests are needed where an ETA anchor is used in a base material that meets the ETA.

To check the installation (proof tests): not needed where an ETA anchor is designed, selected and installed as its ETA requires, by a competent person under supervision. Otherwise, or where the specifier asks, a sample is proof tested. Some anchors are not usually tested at all: light-duty non-structural plastic anchors, small concrete screws, self-drilling screws, gas and powder-actuated pins, and cast-in bolts and channels. See when to site test anchors.

Who does what?

  • The specifier designs the connection, chooses the anchor and sets the test plan, the loads and the factors.
  • The installer puts the anchors in as the maker says.
  • The tester carries out the tests and reports what happened, without explaining failures unless qualified in anchor technology.
  • The specifier or responsible engineer decides what the results mean.

For how this works on a programme with many trades, see anchor testing for contractors.

Worked example: discrete areas on one job

A fit-out has 600 anchors: 400 in concrete soffits put in by one team, and 200 in a brick wall put in by another. Different base materials and different teams make them two discrete areas, each sampled on its own.

  • Concrete soffits: 2.5% of 400 = 10 proof tests.
  • Brick wall: 2.5% of 200 = 5 proof tests.
  • Total: 15, and each area has at least 3.

At 2.5% the proof factor is 1.5, so an anchor with N_Ek = 2 kN is proof loaded to 3 kN, provided that's no more than 1.5 times the maker's recommended load.

Testing overhead

A t60 on an anchor in a concrete soffit.

A tester in gloves using a Staht t60 pull tester on an anchor in a concrete soffit overhead

What kit does construction testing need?

On soffits and walls, fix the rig in place so it can't fall if the anchor fails.

What should the test report record?

Facts that let the specifier judge the tests: the job, the anchor and the test asked for, the base material, how the anchors went in, each anchor's position and result, the tester's equipment and calibration, and a sign-off saying the report records facts only. Use our free anchor test report template, or see what a test report should record.

More questions

Izvori

  1. BS 8539:2012+A1:2021 Code of practice for the selection and installation of post-installed anchors in concrete and masonry, BSI
  2. EAD 330499-02-0601 Bonded fasteners and bonded expansion fasteners for use in concrete, EOTA
  3. The Construction (Design and Management) Regulations 2015, regulation 19: Stability of structures, legislation.gov.uk
  4. BS 5975-1:2024 Temporary works. Management procedures for the control of temporary works. Code of practice, BSI
  5. Temporary works, HSE
  6. Staht t25 Digital Pull Tester brochure, Staht
  7. Anchor Pull Test Report: What It Should Record, Staht