I korthet
Post-installed anchors in concrete and masonry are selected, installed and tested under BS 8539:2012+A1:2021. Site tests do two jobs: finding what an anchor can carry where there's no data for the base material, and proof testing a sample of installed anchors to check they went in properly. The specifier sets the tests and loads; the tester records facts; the specifier decides what they mean.
Denna guide förklarar hur provningar på plats planeras och utförs enligt BS 8539:2012+A1:2021. Den ersätter inte standarden, ankartillverkarens data eller anvisningarna från den förskrivare eller konstruktör som ansvarar för uppdraget och som beslutar om provningsplan, laster och faktorer. En provning dokumenterar vad som hände vid provtillfället; den godkänner inte en infästning för användning.
Key figures
| Proof sample | At least 2.5% of anchors and at least 3, with at least 3 in each discrete area |
|---|---|
| Proof load | N_Ek × 1.5 at 2.5% tested, or × 1.25 at 5%; no more than 1.5 × the maker's recommended load |
| Pass | Holds the proof load without movement, or damage to the anchor or base material |
| Allowable-load tests | Mostly in masonry, on anchors installed for the test and not used after |
| Bonded anchors | Tested only after at least the maker's recommended curing time |
Who is this page for?
Fixings installers, main contractors, M&E and façade contractors, and temporary works coordinators: anyone who specifies, installs, tests or relies on anchors drilled into concrete, brick or block. Scaffold tie anchors have their own guidance: see scaffolding.
Which rules and standards apply?
| Document | From | What it means for anchors |
|---|---|---|
| BS 8539:2012+A1:2021 | BSI | The code of practice for selecting and installing post-installed anchors in concrete and masonry, including site tests. Current, under review |
| European Technical Assessments (ETAs) | Assessment bodies, to EOTA's EADs | An anchor's assessed performance and conditions of use. For bonded anchors in concrete the current assessment document is EAD 330499-02-0601 |
| CDM Regulations 2015, regulation 19 | UK legislation | Any temporary support or structure must be "of such design and installed and maintained so as to withstand any foreseeable loads which may be imposed on it" |
| BS 5975-1:2024 | BSI | Procedures for controlling temporary works. It and BS 5975-2:2024 replaced BS 5975:2019, withdrawn in December 2024 |
| Work at Height Regulations 2005 | UK legislation | For anchors used with fall protection on site: see [height safety](/industries/height-safety) |
When do anchors need site tests?
To find what an anchor can carry: only where the maker has no data for the base material. That is rare in concrete, because BS 8539 recommends anchors with an ETA, and is mostly needed in masonry or where the concrete's condition is in doubt. No tests are needed where an ETA anchor is used in a base material that meets the ETA.
To check the installation (proof tests): not needed where an ETA anchor is designed, selected and installed as its ETA requires, by a competent person under supervision. Otherwise, or where the specifier asks, a sample is proof tested. Some anchors are not usually tested at all: light-duty non-structural plastic anchors, small concrete screws, self-drilling screws, gas and powder-actuated pins, and cast-in bolts and channels. See when to site test anchors.
Who does what?
- The specifier designs the connection, chooses the anchor and sets the test plan, the loads and the factors.
- The installer puts the anchors in as the maker says.
- The tester carries out the tests and reports what happened, without explaining failures unless qualified in anchor technology.
- The specifier or responsible engineer decides what the results mean.
For how this works on a programme with many trades, see anchor testing for contractors.
Worked example: discrete areas on one job
A fit-out has 600 anchors: 400 in concrete soffits put in by one team, and 200 in a brick wall put in by another. Different base materials and different teams make them two discrete areas, each sampled on its own.
- Concrete soffits: 2.5% of 400 = 10 proof tests.
- Brick wall: 2.5% of 200 = 5 proof tests.
- Total: 15, and each area has at least 3.
At 2.5% the proof factor is 1.5, so an anchor with N_Ek = 2 kN is proof loaded to 3 kN, provided that's no more than 1.5 times the maker's recommended load.
Testing overhead
A t60 on an anchor in a concrete soffit.

What kit does construction testing need?
On soffits and walls, fix the rig in place so it can't fall if the anchor fails.
- To 25 kN or 60 kN: a t25 or t60, M6 to M16 or M6 to M20, and threaded adaptors that take the M16 drop rod up to M22, M24, M27 or M30.
- Wider tests: modular bridges with 375 mm or 575 mm between the feet, for preliminary tests and tests to failure where leg spacing matters. See bridge leg spacing.
- Shear: the shear test rig, M6 to M20, with a t25 or t60 load cell.
- Large anchors and rebar: the heavy duty kits, 176 kN and 358 kN. See rebar and holding-down bolts.
What should the test report record?
Facts that let the specifier judge the tests: the job, the anchor and the test asked for, the base material, how the anchors went in, each anchor's position and result, the tester's equipment and calibration, and a sign-off saying the report records facts only. Use our free anchor test report template, or see what a test report should record.
More questions
It depends on the fixing and the specification. Light-duty non-structural plastic anchors, small concrete screws, self-drilling screws and pins are not usually tested, and an ETA anchor installed as its ETA requires by a competent person under supervision doesn't need proof tests unless the specifier asks.
No. Site tests show performance only in uncracked concrete. Where an anchor is designed for concrete in tension, the specifier uses a condition factor of 0.7 when working out a preliminary test load, which raises the load.
Only on a specialist's or the anchor maker's advice. A competent installer fits the replacement, the specifier confirms the specification and chooses any new hole positions.
Only after at least the curing time the maker recommends for the temperature on site.
Källor
- BS 8539:2012+A1:2021 Code of practice for the selection and installation of post-installed anchors in concrete and masonry, BSI
- EAD 330499-02-0601 Bonded fasteners and bonded expansion fasteners for use in concrete, EOTA
- The Construction (Design and Management) Regulations 2015, regulation 19: Stability of structures, legislation.gov.uk
- BS 5975-1:2024 Temporary works. Management procedures for the control of temporary works. Code of practice, BSI
- Temporary works, HSE
- Staht t25 Digital Pull Tester brochure, Staht
- Anchor Pull Test Report: What It Should Record, Staht