Guide: United States

Anchor pull test requirements in the US

Ukratko

In the US, fall protection anchorages must hold 5,000 lb (22.2 kN) per person attached, or be designed with a safety factor of at least two under a qualified person (OSHA). Building owners must have rope descent anchorages tested and certified, inspected every year and certified at least every 10 years. No federal rule sets the test load: the qualified person or engineer does.

Ova stranica objašnjava kako se sidra, vijci s okom i sidrišne točke uobičajeno ispituju, pregledavaju i bilježe. Ne zamjenjuje zakon, norme koje navodi, proizvođačeve upute niti odluke osobe odgovorne za posao ili sustav, koja određuje ispitivanja, opterećenja i režim pregleda. Ispitivanje bilježi što se dogodilo na dan; ne odobrava sidro za uporabu.

Key figures

OSHA anchorage strength5,000 lb (22.2 kN) per person attached, or a qualified person's design with a safety factor of at least 2
Rope descent anchoragesInspected every year; certified by a qualified person at least every 10 years (1910.27)
Test load OSHA accepted in 20192,500 lb, twice a 1,250 lb design load; 5,000 lb where a consensus standard or the qualified person calls for it
Field test methodASTM E3121/E3121M, for anchors in concrete or masonry
Staht t25 and t600 to 25 kN (5,620 lbf) and 0 to 60 kN (about 13,490 lbf)

What is anchor testing called in the US?

Most often anchor pull testing, proof load testing or load testing. Engineers and inspectors also say tension testing (with torque testing for anchors set by torque), and California's building code says proof test. For roof and window washing anchors the job is usually sold as anchor inspection and certification, or recertification. On construction projects, post-installed anchors come under special inspection, and proof tests are often specified alongside it.

The tool is an anchor pull tester or anchor tester. US sellers give its range in pounds (lb or lbf) as well as kN.

What does OSHA require of a fall protection anchorage?

Both OSHA's construction rule (29 CFR 1926.502(d)(15)) and its general industry rule (29 CFR 1910.140(c)(13)) give two ways to comply. An anchorage for personal fall arrest either:

  • holds at least 5,000 lb (22.2 kN) for each person attached; or
  • is designed, installed and used as part of a complete fall arrest system with a safety factor of at least two, under the supervision of a qualified person.

OSHA defines a qualified person by a recognised degree, certificate or professional standing, or by extensive knowledge, training and experience. Neither rule says how an anchorage is tested.

What does OSHA require for window washing and rope descent anchorages?

For rope descent systems, such as those used for window washing, 29 CFR 1910.27(b)(1) puts the duty on the building owner. Before anyone uses one, the owner must tell the employer in writing that each anchorage has been identified, tested, certified and maintained to hold at least 5,000 lb in any direction for each person attached. That assurance rests on:

  • an inspection every year by a qualified person; and
  • certification of each anchorage by a qualified person, as necessary and at least every 10 years.

Owners had to comply by 20 November 2017. OSHA's enforcement guidance of that date let inspectors use discretion, case by case, where an owner whose anchorages weren't yet certified could document due diligence, such as evidence it had contacted a qualified person to inspect, test and certify them.

What load should an anchorage be pull tested to?

No federal rule says. In a letter of 25 January 2019 on testing rope descent anchorages, OSHA said its standard sets no testing criteria, so a qualified person may use any scientifically valid ones. The question it answered quoted the window cleaning standard ANSI/IWCA I-14.1 (2001 edition), which calls for a static test at twice the design load in each primary direction a load may be applied. OSHA accepted that example, an anchorage of 5,000 lb ultimate strength with a four-to-one safety factor, so a 1,250 lb design load, tested to 2,500 lb (about 11.1 kN), and said testing to the full 5,000 lb would also be acceptable where a consensus standard calls for it or the qualified person judges it necessary.

Oregon, which runs its own OSHA state plan, read the rule more strictly. In letter SI 2018-01 (6 February 2018, a year before the federal letter), Oregon OSHA said it took the rule to require tests to 5,000 lb in all directions, but recorded a window cleaning firm's report that such tests had, many times, left anchorages deformed. So in Oregon, an owner who instead has a registered professional engineer evaluate each anchorage in a written report, and then has a testing organisation static load test it to at least 2,500 lb in each direction it could be loaded, commits only what Oregon OSHA will treat as a de minimis violation.

In practice, the test load comes from the qualified person or engineer, from the anchorage's design and its maker's instructions. A higher test isn't automatically a better one: it can damage the anchor it's meant to check.

US anchorage figures in pounds and kN

FigurePoundskNWhere it comes from
Anchorage strength per person attached5,000 lb22.2 kNOSHA 1926.502(d)(15) and 1910.140(c)(13)
Test at twice a 1,250 lb design load2,500 lbabout 11.1 kNOSHA letter of 25 January 2019
Oregon's alternative static test, each directionat least 2,500 lbabout 11.1 kNOregon OSHA SI 2018-01
Staht t25 range0 to 5,620 lbf0 to 25 kNStaht t25 data sheet and manual
Staht t60 range0 to about 13,490 lbf0 to 60 kNStaht t60 data sheet; lbf worked out

1 kN is about 224.8 lbf, so 5,000 lb is 22.24 kN, which OSHA rounds to 22.2 kN. Pounds worked out here are rounded to the nearest 10, except the small accuracy figures.

How are post-installed anchors in concrete tested?

On building and civil projects, anchors drilled and fixed into hardened concrete are checked through special inspection, and pull tests where the design calls for them:

  • ASTM E3121/E3121M (current as E3121/E3121M-17, reapproved 2026) gives the methods for field testing anchors in concrete or masonry, in tension and shear: either to find the ultimate load, or to apply a proof load that checks an anchor was installed properly. ASTM leaves the choice of tests to whoever specifies them.
  • ASTM E488/E488M covers testing the strength of anchors in concrete test members, the basis for product evaluation, rather than checking anchors on site.
  • ACI 355.2 (mechanical anchors) and ACI 355.4 (adhesive anchors) set how anchors are tested and qualified for design under ACI 318. ICC-ES issues evaluation reports for anchors against its acceptance criteria AC193 (mechanical anchors) and AC308 (adhesive anchors and reinforcing bars).
  • The International Building Code (Table 1705.3 of the 2024 edition, as reproduced in Georgia's published state amendment) asks for special inspection of anchors post-installed in hardened concrete: continuous for adhesive anchors installed horizontally or upwardly inclined to resist sustained tension, periodic for the rest. Where the anchor's evaluation report gives no inspection requirements, the registered design professional sets them and the building official approves them.
  • California goes further for its public schools and hospitals: section 1910A.5 of the California Building Code sets the proof tests for post-installed anchors, including how often they are tested, and its 2025 edition names ASTM E3121 for the tension test. The Division of the State Architect's IR 25-3 (suspended gypsum board ceilings; its 2022-code edition is the latest DSA lists), for example, has post-installed anchors in concrete for new hanger wires tested at a frequency of 10% to at least 200 lb, and those for bracing wires at 50% to at least 440 lb, with the project or special inspector present.

On these jobs the contract documents say which anchors to test, how many and to what load. Check the edition, and any state or local amendments, your project is built under.

Who is responsible for the testing?

  • Rope descent and window washing anchorages: the duty sits with the building owner, who must have each anchorage inspected every year and certified by a qualified person (29 CFR 1910.27(b)(1)); OSHA's 2017 enforcement guidance describes owners contracting a qualified person to do this. Firms selling the service call it "window washing anchor inspection" and "recertification", and some include load testing and a report sealed by a professional engineer.
  • Other fall protection anchorages: the employer must make sure each anchorage meets OSHA's strength rule: 5,000 lb per person attached, or a qualified person's design with a safety factor of at least two. The system, anchorage included, must be inspected before each use (construction) or before first use in each workshift (general industry). OSHA sets no load test for these anchorages.
  • Post-installed anchors on a construction project: the anchor's evaluation report, or failing that the registered design professional, sets the special inspection, and the contract documents list the tests. On California's DSA projects, field tests are done in the presence of the project inspector or a special inspector.

Whoever pulls the anchor needs a tester whose range covers the test load, a current calibration, and a record that ties each result to its anchorage.

Which Staht tester for US anchor tests?

  • Roof, davit and window washing anchors to 5,000 lb: the t25 reads to 25 kN (5,620 lbf), in kN or lbf, so it covers both a 2,500 lb test and a 5,000 lb one. Its clevis fits an anchor's eye; the anchor jaw and threaded washers fit studs and bolts (connecting a tester to the anchor).
  • Larger anchors and bolts: the t60 reads to 60 kN (about 13,490 lbf).
  • Rebar and heavy anchors: Staht's heavy duty kits reach 176 kN (about 39,570 lbf) and 358 kN (about 80,480 lbf).
  • Lifelines: the LT swage tester and the in-line kit use the t25 load cell, to 25 kN (5,620 lbf).

The t25 and t60 load cells are accurate to ±1.5% of full scale: ±0.375 kN (about ±84 lbf) on the t25 and ±0.9 kN (about ±202 lbf) on the t60. The screen shows live and peak load together, and the free Staht Connect app records each test with a photo, a map pin and the time, for the anchorage file.

Staht's US distributor is Diversified Fall Protection (head office Westlake, Ohio, with an office in Overland, Missouri), which sells, services and calibrates Staht kits: see where to buy.

What should the test record show?

For each anchorage: its identification and place on the roof plan, what it is and what it's fixed into, the load applied (with units) and how long it was held, what was seen during and after, and the result. For the visit: the date, the qualified person, and the tester's make, serial number and calibration date. Our free proof load test record has these fields, and roof anchor and eyebolt testing walks through a set-up.

More questions

Sources

  1. 29 CFR 1926.502, Fall protection systems criteria and practices, OSHA
  2. 29 CFR 1910.140, Personal fall protection systems, OSHA
  3. 29 CFR 1910.27, Scaffolds and rope descent systems, OSHA
  4. RDS anchorage testing certification, letter of interpretation, 25 January 2019, OSHA
  5. Enforcement guidance for general industry rope descent system anchorage requirements, 20 November 2017, OSHA
  6. Testing of rope descent system anchorages on buildings, SI 2018-01, Oregon OSHA
  7. Standard Test Methods for Field Testing of Anchors in Concrete or Masonry, ASTM International
  8. Standard Test Methods for Strength of Anchors in Concrete Elements, ASTM International
  9. Post-Installed Mechanical Anchors in Concrete: Qualification Requirements and Commentary (preview), American Concrete Institute
  10. Post-Installed Adhesive Anchors in Concrete: Qualification Requirements and Commentary (preview), American Concrete Institute
  11. AC193 Mechanical Anchors in Concrete Elements, ICC-ES
  12. AC308 Post-installed Adhesive Anchors and Reinforcing Bars in Concrete Elements, ICC-ES
  13. IBC 2024 Table 1705.3, as amended for Georgia (Amendment 30), Georgia Department of Community Affairs
  14. Use and Inspection of Adhesive Anchors in Federal-Aid Projects, Technical Advisory T 5140.34, Federal Highway Administration
  15. 2025 Part 2 Chapters 19 and 19A Concrete: summary of changes, California Building Standards Commission
  16. Regular fall protection inspection and recertification services, Diversified Fall Protection (Staht's US distributor)
  17. IR 25-3 Suspended Gypsum Board Ceiling, Division of the State Architect

Pull test anchorages up to 5,620 lbf

The t25 reads in kN or lbf, with the free Staht Connect app for records.

Vaša košarica

Učitavanje košarice…