Guide: New Zealand

Anchor testing and recertification in New Zealand

Kurz gesagt

WorkSafe New Zealand says permanent anchors and lifelines should be inspected and recertified at least once a year by a competent person, and building owners, facilities managers and property managers are responsible. Chemically fixed anchors are load tested when installed and every year. Scaffold tie anchors get pull tests on 3 anchors or 5% of them, whichever is more.

Diese Seite erklärt, wie Dübel, Ringschrauben und Anschlagpunkte üblicherweise geprüft, inspiziert und protokolliert werden. Sie ersetzt weder das Gesetz noch die darin genannten Normen, die Anleitung des Herstellers oder die Entscheidungen der für den Auftrag oder das System verantwortlichen Person, die Prüfungen, Lasten und Inspektionsregime festlegt. Eine Prüfung hält fest, was am Tag der Prüfung geschehen ist; sie genehmigt keinen Dübel für den Gebrauch.

Key figures

RecertificationAt least once a year, by a competent person (WorkSafe NZ, 2023 and 2026)
Chemically fixed anchorsLoad tested on installation and every year as part of recertification
Proof load warningAxial proof loads above 50% of the design criteria are likely to weaken an anchor
Pull tester calibrationBy a company accredited by IANZ, with its certificate kept with the tester
Scaffold tie anchorsPull tests on 3 anchors or 5%, whichever is more, recorded

What is it called in New Zealand?

WorkSafe's own word is recertification: permanent anchors and lifelines are inspected and recertified, and tagged. Contractors sell height safety system certification and recertification, and abseil anchor audits. The test is a load test, pull test or proof load. Designers are Chartered Professional Engineers (CPEng), who sign producer statements; the person inspecting is a competent person.

What does WorkSafe say about permanent anchors?

WorkSafe's safety alert of 10 May 2023, Maintaining, inspecting and re-certifying permanent anchorage systems, says:

  • permanently installed anchors and lifeline systems need maintaining, inspecting and recertifying after installation;
  • they should be inspected and recertified at least annually by a competent person, as part of the building's maintenance programme;
  • the inspector should see documents showing a Chartered Professional Engineer designed and approved the system;
  • anyone using a system should check it was recertified within the last year, and inspect it before use.

It names building owners, facilities managers and property managers as responsible, and says many of them don't know about these requirements.

WorkSafe's good practice guidelines Working at height in New Zealand (August 2026) say every fall arrest and abseil anchor should be tagged and recertified annually, each permanent anchor should be designed by a chartered professional engineer, and each should be uniquely identified so its installation, testing and maintenance can be tracked.

How are rope access anchors tested?

The Industrial Rope Access in New Zealand best practice guidelines (published by IRAANZ with the Department of Labour, May 2012), the guidance WorkSafe's alert points owners to, say:

  • anchors should be inspected and tested at least every 12 months, or as the design engineer or maker specifies, with a log for each permanent anchor;
  • proof loading friction anchors is part of the examination, but an axial proof load above 50% of the design criteria is likely to weaken the anchor or shorten its life;
  • chemically fixed anchors are load tested when installed and every year as part of annual recertification;
  • permanent anchors should have a maximum life of 10 years unless the maker gives less; where the design life is longer, a certified engineer or the maker should review them at 10 years;
  • a CPEng confirms the anchors were installed correctly with a PS4 producer statement (construction review);
  • pull-test equipment should be calibrated by a company accredited by IANZ, with its calibration certificate kept with it, and the people testing must be competent and trained.

Do scaffold tie anchors need pull testing?

Yes. WorkSafe's Scaffolding in New Zealand good practice guidelines say ties using chemical or mechanical anchors should have pull tests on 3 anchors or 5% of them, whichever is more, covering each type of anchor, base material and installer, with the results recorded. Drilled-in anchors loaded in tension should be used only where no other tie is practicable, with a safety factor of 3, assessed by a competent person. NZQA's scaffolding ties skill standard (41206) includes testing the tie anchors to those guidelines and the anchor maker's specification.

For how a tie test is done, the UK method is set out in scaffold tie proof testing.

Which standards apply?

  • AS/NZS 1891.4:2025, the joint Australian and New Zealand standard for selecting, using and maintaining fall arrest equipment, anchors included, published on 19 September 2025. It replaced the 2009 edition that WorkSafe's 2023 alert names.
  • AS/NZS 5532:2013, single-point anchor devices, has been replaced in Australia by AS 5532:2025, an Australian-only standard. Check with Standards New Zealand which edition applies to your job.

Roof anchors have no entry of their own in the list of specified systems for a building's compliance schedule, as MBIE's Compliance Schedule Handbook sets it out. Their yearly recertification comes from WorkSafe's guidance. Ask your council or IQP whether your building's compliance schedule takes in anchors as part of another system, such as building maintenance units (SS 10).

Which Staht tester?

  • Roof, abseil and fall arrest anchors: the t25, to 25 kN. Its clevis fits an anchor's eye; the anchor jaw and threaded washers fit studs and bolts.
  • Larger anchors: the t60, to 60 kN.
  • Lifelines: the LT swage tester and in-line kit, with the t25 load cell, to 25 kN.

The t25 and t60 load cells are accurate to ±1.5% of full scale, ±0.375 kN and ±0.9 kN. The free Staht Connect app records each anchor's test with a photo, a map pin and the time, to build the log for each uniquely numbered anchor.

For dealers in New Zealand, see where to buy. Ask your dealer or calibration house whether its calibration is IANZ accredited, as the rope access guidelines ask.

What should the record show?

For each anchor: its unique number and tag, where it is, what it's fixed into, the load and hold, what was seen, and the result, with photos. For the visit: the date, the competent person, and the tester's make, serial number and calibration certificate. Our free proof load test record has fields for each anchor's reference, location, load, hold and result, and for the tester and its calibration; keep the photos and tag details with it. For Australia, see anchor point testing in Australia.

More questions

Sources

  1. Maintaining, inspecting and re-certifying permanent anchorage systems (safety alert, 10 May 2023), WorkSafe New Zealand
  2. Working at height in New Zealand (good practice guidelines, August 2026), WorkSafe New Zealand
  3. Industrial Rope Access in New Zealand: Best Practice Guidelines (2012), IRAANZ with the Department of Labour (hosted by WorkSafe New Zealand)
  4. Scaffolding in New Zealand (good practice guidelines, 2016), WorkSafe New Zealand
  5. 41206 Design, erect, and dismantle scaffolding ties and repair attachment points, NZQA
  6. Compliance Schedule Handbook, Amendment 3 (February 2014), specified systems list, MBIE (building.govt.nz)
  7. Spotlight on AS/NZS 1891.4:2025, Standards Australia

Recertify anchors with a t25

Tests to 25 kN, with the free Staht Connect app for each anchor's log.

Ihr Warenkorb